SIMPLE SOLUTIONS

RICHCOMM_USB(8) - man page online | administration and privileged commands

Driver UPS equipment using Richcomm dry-contact to USB solution.

Chapter
02/15/2014
RICHCOMM_USB(8)                             NUT Manual                            RICHCOMM_USB(8)

NAME richcomm_usb - Driver UPS equipment using Richcomm dry-contact to USB solution
NOTE This man page only documents the specific features of the richcomm_usb driver. For information about the core driver, see nutupsdrv(8).
SUPPORTED HARDWARE The Richcomm dry-contact to USB solution is a generic interface that is used to upgrade an existing (RS-232) contact closure UPS interface to USB. As such, all the limitations of the underlying contact closure interface apply. This means that you will only get the essentials in ups.status: OL, OB, and LB. See also genericups(8).
BUGS Most contact-closure UPSes will not power down the load if the line power is present. This can create a race when using slave upsmon(8) systems. See the upsmon(8) man page for more information. The solution to both of these problems is to upgrade to a smart protocol UPS of some kind that allows detection and proper load cycling on command.
AUTHORS Peter van Valderen <p.v.valderen at probu.nl>, Dirk Teurlings <dirk at upexia.nl>
SEE ALSO The core driver: nutupsdrv(8) The generic serial driver: genericups(8) Internet resources: The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
Network UPS Tools 2.7.1. 02/15/2014 RICHCOMM_USB(8)
This manual Reference Other manuals
richcomm_usb(8) referred by nutupsdrv(8)
refer to genericups(8) | nutupsdrv(8) | upsmon(8)